Anupam Paints
SolutionsWater & Chemical
💧

Tank Lining Systems

Potable Water, Chemical, Fuel Tanks

Total DFT
300-800 microns
Service Life
15-20 years
Environment
Im1/Im2/Im3 (Immersion)
Layers
2 coat system

Solventless and food-grade lining systems for potable water tanks, fuel storage tanks, chemical tanks, and effluent treatment plants. WRAS and FDA approved for drinking water contact.

Coating System — Layer by Layer

1
Primer100% solids epoxy

Solventless Epoxy Tank Lining (self-priming)

Self-priming — direct application to blasted steel. Zero VOC.

DFT: 150-250 microns
Coats: 1
Airless spray (heated)
2
Build/Finish100% solids epoxy

Solventless Epoxy Tank Lining

Seamless, non-porous barrier. WRAS approved for potable water.

DFT: 150-250 microns
Coats: 1
Airless spray (heated)

Surface Preparation

  • Blast cleaning to Sa 3 (white metal)
  • Surface profile 50-100 microns
  • Solvent wipe to remove all contamination
  • Strict humidity and temperature controls

Applicable Standards

WRAS (UK)FDA 21 CFRAWWA C210IS 15489NSF 61

Applications

  • Overhead water tanks (OHT)
  • Underground water tanks (UGT)
  • Water treatment plant structures
  • Fuel storage tanks
  • Chemical storage tanks
  • ETP structures
  • Swimming pools

Why Anupam Paints

  • WRAS approved — UK standard for potable water
  • FDA 21 CFR compliant for food contact
  • Zero VOC — 100% solids
  • Supplied to municipal water projects

Need This Coating System?

Our technical team will prepare a detailed specification and competitive quotation for your project.

Chat with us